Casa de la Vila (City Council building) Barcelona

Building view

 

Tester building (with a single party wall) with a rectangular PB+3 plant and basement plant, built in 1850 for use by city council central offices and the city council data centre. It is a building with the predominance of the solid over the openings. Although itwas rehabilitated in 2010, its opaque closures have no thermal insulation. Rehabilitation of 2010 did include a replacement of existing windows for other air-chambered aluminium ones on the plants P1, P2, and P3, but on the ground floor the frame was changed, but not the glass. The openings have wood slats as solar protections.

 

characteristics

Location: Plaça Ajuntament, 1, 08830 Sant Boi de Llobregat, Barcelona

Building geometry:

Gross total area: 2.431,62 m²

Total built volume: 6.028,5 m3

Number of floors: subterranean floor + base floor + 3 floors

Floor height: Base floor: 3,5m / Rest of floors: 2,8 

Wall construction:

The building walls are monolithic walls, 30 cm wide with no insulation.

External wall: 2.02 W/m²K

Ground wall: 0.99 W/m²K

Flat roof: 0.5 W/m²K

Windows (double glazed): 3 / 5.6 W/m²K

Heating and cooling system:

Indicator

Zone

Typology

Capacity

Heating system

Offices

Reversible heat pump

255 kW

Underground and Plenary room

2x Reversible heat pumps

2x 13.5 kW

Second floor

Heat  pump  Split  air  conditioning system

Heat pump Multi-Splitair conditioning  system  (two  indoor units)

Autonomous     system    of    heat pumps  with  split  type  refrigerant that  serves  the  computer  room (CPD)

Autonomous     system    of    heat pumps  with  split  type  refrigerant that  serves  the  computer  room (CPD)

 

8.2 kW

4.4 kW

11.2 kW

 

8 kW

DHW system

n/a

Cooling system

Offices

Reversible heat pump

211 kW

Underground and Plenary room

2x Reversible heat pumps

2x 12 kW

Second floor

Heat  pump  Split  air  conditioning system

Heat pump Multi-Splitair conditioning  system  (two  indoor units)

Autonomous     system    of    heat pumps  with  split  type  refrigerant that  serves  the  computer  room (CPD)

Autonomous     system    of    heat pumps  with  split  type  refrigerant that  serves  the  computer  room (CPD)

 

 

7.1kW

4.0kW

9.6 kW

 

2x 6.75 kW

Since 2020 a renewal system has been installed that allows free-cooling. The installation works by default by means of a CO2 probe but it is also activated in summer when the outside temperature is lower than the inside temperature. As it is a plenary room with high thermal loads, this extra ventilation does not only occur at night.

Illumination:

The building’s lighting consists, mainly, of tl8 fluorescent screens with electromagnetic ballast and downlight with low-power fluorescent lamps. Very punctually, some halogen lamp can be found. The system has low degree of division in sectors and no area has regulatory and control devices. At the same time the number of hours of lightening is between 2,450-3,120 hours depending on the space. There is no use of natural light primarily for two factors: the lack of installation sector and the small dimension of the openings.

Energy consumption:

Total energy consumption

Energy  consumption  per  end use

Electricity consumption: ≈270832 kWh/year

Electricity price: ≈0.15 €/kWh

Space Heating: 38249,64 kWh/year

Space cooling: 67334,80 kWh/year

Domestic Hot Water: 0 kWh/year

Electrical devices: ≈ 150000 kWh/year

Computer server electricity: ≈ 48186.5 kWh/year

Suppliers about the building